Placeholder

FIBERGLASS TOWERS

0 out of 5

Category: .

Cooling Towers 45 to 540 Tons

Temptek tower cells are designed to cool water through evaporation. Cooling towers are part of a central system (complete with a pump tank station). Tower cells supply temperatures to 85° (depending on ambient air heat and humidity) and are installed outside the plant building, either elevated on a stand or mounted on the roof. These tower cells are made of durable UV protected fiberglass with a counter air flow design.

TOWER DESIGN:
• Single or multi cell designs
• Total non-ferrous construction materials
• Single inlet and drain connections on models up to 270 tons
• Induced draft air movement
• Structural galvanized steel base on 45 to 135 ton models
• Structural painted steel base on 170 to 540 ton models

SHELL CONSTRUCTION:
• High strength fiberglass molding
• 1/2” of structural thickness in reinforced areas
• UV stabilized coating
• Acrylic adhesive bonding between shell halves
• Polyurethane sealant

FAN:
• Air foil shaped blades for increased air flow
• Blades are made of a glass fiber reinforced polymer
• Direct drive
• Factory set for maximum air movement

MOTOR:
• TEFC construction
• Mounted on a stainless steel frame
• Supported on reinforced fiberglass shell area
• Mounted to shell with stainless steel fasteners

INLET LOUVERS:
• PVC construction
• Easily removed for cleaning
• Vertical orientation to eliminate ‘splash out’
• Directs air flow at proper angle for even distribution
• Helps prevent air-born debris from entering cell

DISTRIBUTION HEADER:
• Non-ferrous PVC ‘cross’ construction
• Stationary
• Computer designed spray pattern
• Large orifice spray heads
• PVC spray heads
• Drift eliminator prevents over spray and water loss

WET DECK:
• Stacked honeycomb pattern maximizes water and air flow for greater cooling efficiency
• PVC construction

INSPECTION COVERS:
• Easily removed
• Seamless gasket sealing
• Allows for inspection of cell interior and replacement of wet deck

WARRANTIES:
• 10 year shell warranty
• 5 year motor/fan warranty

OPTIONS:

FAN STARTER KIT:
• Motor starter contactor
• Motor overload relay
• Nema 1 enclosure
• Fan thermostat

SIDE OUTLET:
• PVC flange
• Factory installed

BASIN FLOAT VALVE:
• Mechanical float and valve
• 1/2” supply connection
• Factory or field installed

TOWER STAND:
• 10’ corner post design with cross bracing
• Ladder and railing attachments

TP SERIES SPECIFICATIONS

MODEL
T45P
T85P
T105P
T135P
T170P
T210P
T270P
T315P
T405P
T540P
CAPACITY TONS
45
85
105
135
170
210
270
315
405
540
CAPACITY FLOW RATE GPM
135
255
315
405
510
630
810
945
1215
1620
FAN QUANTITY
1
1
1
1
2
2
2
3
3
4
FAN RPM
1170
1170
1170
870
1170
1170
870
1170
870
870
# BLADES PER FAN
9
9
9
6
9
9
6
9
6
6
FAN DIAMETER
36
42
42
60
42
42
60
42
60
60
TOTAL CFM
12040
21700
25000
30500
43400
50000
61000
78388
91500
122000
# MOTORS
1
1
1
1
2
2
2
3
3
4
TOTAL HP
3
5
10
7.5
10
20
15
30
22.5
30
FULL LOAD AMPS @ 230 / 3 / 60
9.6
15.2
28
28
28
56
56
86.4
84
112
FULL LOAD AMPS @ 460 / 3 / 60
4.8
7.6
14
14
14
28
28
43.2
42
56
PIPE SIZE TO PROCESS
3″
4″
4″
4″
6″
6″
6″
2 X 6″
2 X 6″
2 X 6″
PIPE SIZE FROM PROCESS
4″
6″
6″
6″
10″
10″
10″
2 X 10″
2 X 10″
2 X 10″
DIMENSION HEIGHT
138″
138″
143″
140″
138″
143″
140″
143″
140″
140″
DIMENSTION LENGTH
60″
84″
84″
96″
145″
145″
169″
217″
254″
338″
DIMENSION DEPTH
49″
73″
73″
85″
84″
84″
96″
84″
96″
96″
WEIGHT DRY LBS
725
1290
1390
1612
2310
2210
3125
4000
4350
5800
WEIGHT OPERATING LBS
1470
3100
3200
4200
5700
5600
7800
10700
11000
15000
WEIGHT SHIPPING LBS
1100
1580
1680
1950
2310
2710
3125
4000
4350
5800